Part Number Hot Search : 
B2322BS1 VN2460 5EETT LP1500 BGX885 TMP05 5NCF10KE DT54F
Product Description
Full Text Search
 

To Download 104601 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  ? phoenix contact 2012-05-21 104601_en_04 macx mcr-ex-t-ui-up... data sheet 1description the configurable and programmable macx mcr-ex-t-ui-up... temperature transduc er is used for the intrinsically safe (ex i) operat ion of all standard temperature sensors (rtds and thermocouples), voltage signals, re- mote resistance-type sensors and potentiometers. the tem- perature input signals are output in a linearized format at the output. in addition to an analog current and voltage output, the module also has a switching output. the power supply has been designed as a wide range power supply. the devices can be installed in zone 2 in the protection type ?n? (en 60079-15). the temperature transducer ca n be configured with the standard configuration (see example: ?order key? on page 6) or order-specific according to the order key and is delivered calibrated and ready for operation. possible set- tings for the modules configured according to the order (macx mcr...-c) can be found in the order key on page page 6. the set configuration is shown on the label on the side of the housing. features such as sensor type, connection method, measur- ing range, measuring unit, filter, alarm signal and output range can be configured using the ifs-conf software and a device-specific dtm (device type manager). features ? input for all standard temperature sensors (rtds and thermocouples), voltage signals, remote resistance- type sensors and potentiometers. ? with intrinsically safe inputs [ex ia] iic ? current and voltage output ? switching output (1 pdt relay) ? configuration via software (fdt/dtm) or operator inter- face (ifs-op-unit) ? up to sil 2 according to en 61508 on output 4 ... 20 ma ? 3-way electrical isolation ? installation in zone 2 permitted ? wide range power supply 19.2 ... 253 v ac/dc ? with screw or spring-cage connection warning: explosion hazard the device is an item of associated electrical equipm ent for intrinsically safe circuits. it is designed for use in zone 2, if specific conditions are observed. when installing and operating the device, the applicable safety directives (inclu ding national safety directives), ac- cident prevention regulations, as well as ge neral technical regulations must be observed. warning: explosion hazard please observe the safety regulations and installation notes on page 11. make sure you always use the latest documentation. it can be downloaded at www.phoenixcontact.net/catalog . this data sheet is valid for the produc ts listed in section 3 ?ordering data? . temperature transducers wi th intrinsically safe input for temperature sens ors, voltage signals, resistance-type sensor s and potentiometers
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 2 2table of contents 1 description................................................................................................................... ............... 1 2 table of contents ............................................................................................................. ........... 2 3 ordering data................................................................................................................. ............. 5 4 order key ..................................................................................................................... .............. 6 5 technical data ................................................................................................................ ............ 7 6 minimum span and measuring accuracies.................................................................................. 9 6.1 pt and ni-rtd inputs ............................................................................................................................... ......... 9 6.2 cu-rtd inputs ............................................................................................................................... .................... 9 6.3 ni1000 input (landis & gyr), kty 81-110, kty 84-130 (philips) .............................................................. 9 6.4 thermocouple input ............................................................................................................................... ........... 9 6.5 cold junction error......................................................................................................... ...................... 9 6.6 voltage signal input ............................................................................................................................... ........... 9 6.7 r transducers and resistors ............................................................................................................................ 9 6.8 potentiometer ............................................................................................................................... ................... 10 6.9 output signals ............................................................................................................................... .................. 10 7 safety regulations and installa tion notes.................................................................................... 11 7.1 installation and operation ............................................................................................................................... 11 7.2 safety regulations for installati on in potentially explosive areas .............................................................. 11 7.3 use in safety-related applications (sil 2) .................................................................................................... 12 8 installation .................................................................................................................. ............... 13 8.1 basic circuit diagrams ............................................................................................................................... .... 13 8.2 structure ............................................................................................................................... ............................ 13 8.3 dimensions ............................................................................................................................... ....................... 14 8.4 mounting ............................................................................................................................... ........................... 14 8.5 connecting the cables ....................................................................................................... ............... 14 8.6 power supply ............................................................................................................................... .................... 14 8.7 sensor types ................................................................................................................ ..................... 15 8.7.1 thermocouple (tc) with internal cold junction co mpensation ................................................................ ...... 15 8.7.2 thermocouple (tc) with external or without cold junction compensation..................................................... 15 8.7.3 voltage input ............................................................................................................. ................................... 15 8.7.4 potentiometer ............................................................................................................. .................................. 15 8.7.5 resistance thermometer (rtd).............................................................................................. ...................... 15 8.7.6 measuring resistances ..................................................................................................... ............................ 15 8.8 current output ............................................................................................................................... .................. 15 8.9 voltage output ............................................................................................................................... .................. 15 8.10 switching output........................................................................................................... ..................... 16
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 3 8.11 switching output behavior with manual acknowledgement (latching) .................................................... 17 8.11.1 switching behavior (2): undertemperature limit ( sph) .............................................................................. 17 8.11.2 (switching behavior (3 ): overtemperature limit ( sph) ............................................................................... 17 8.11.3 switching behavior (4): undert emperature limit with hysteresis ( spl) ...................................................... 18 8.11.4 switching behavior (5): overte mperature limit with hysteresis ( sph)........................................................ 18 8.11.5 switching behavior (6): temperature range limit ( spl and sph) ........................................................... 19 8.11.6 switching behavior (7): temperature range limit ( spl and sph) ........................................................... 19 8.12 monitoring function ............................................................................................................................... .......... 20 8.13 operating modes ............................................................................................................................... ............. 20 8.13.1 sil on/sil off ........................................................................................................... ................................ 20 8.13.2 service mode ............................................................................................................. .................................. 20 9 configuration ................................................................................................................. ............ 20 9.1 delivered state/standard configuration ........................................................................................................ 21 9.2 zero adjust, adjustment via buttons s2 and s3 (only possible with sil off) ....................................... 21 9.3 span adjust, adjustment via buttons 2 and 4 (only possible with sil off) ............................................ 21 9.4 force output................................................................................................................ ...................... 21 9.5 cable compensation, 2-wire rtd or rtd 1 with 2 x rtd ........................................................................ 21 9.6 cable compensation rtd 2 with 2 x rtd or tc wi th external cold junction compensation (tc + cj external) ............................................................................................................................... ............................ 22 9.7 automatic potentiometer adjustment (teach-in) ......................................................................................... 22 9.8 manual acknowledgement of sw itching outputs (latch function) .............................................................. 22 9.9 led status indicators ....................................................................................................... ................. 22 10 password..................................................................................................................... .............. 23 11 flow chart, operator in terface ............................................................................................... ..... 23 11.1 menu structure ............................................................................................................................... ................. 24 11.2 key for start screen ............................................................................................................................... .......... 25 11.3 key for settings - menu .......................................................................................................................... 25 11.4 key for settings - configure ..................................................................................................................... 25 11.5 key for settings - service ......................................................................................................................... 26 11.6 key for settings - save ............................................................................................................................. 26 11.7 key for input ............................................................................................................................... ...................... 27 11.7.1 key for input configuration (analog input) ............................................................................... ...................... 27 11.8 key for output ............................................................................................................................... ................... 29 11.8.1 key for output configuration (analog output)............................................................................. .................... 29 11.9 key for error handling ............................................................................................................................... ...... 30 11.10 key for switch ............................................................................................................................... ................... 30
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 4 12 ifs-op-unit operator interfac e error codes ............................................................................. 30 13 configuration with the service pc ............................................................................................ .. 31 13.1 system requirements ............................................................................................................................... ...... 31 13.2 configuring the user characteristic curve .................................................................................. ........ 31 14 comparison of safety data .................................................................................................... ..... 31 15 application examples......................................................................................................... ........ 32 15.1 current output ............................................................................................................................... .................. 32 15.2 voltage output ............................................................................................................................... .................. 32 15.3 switching output ............................................................................................................................... ............... 33 appendix safety-related applications (sil 2) ............................................................................................................................. a- 1
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 5 3ordering data temperature transducer, ex i description type order no. pcs. / pkt. standard configuration/in-stock article, with screw connection macx mcr-ex-t-ui-up 2865654 1 standard configuration/in-stock article, with spring-cage connection macx mcr-ex-t-ui-up-sp 2924689 1 order configuration/kmat, with screw connection macx mcr-ex-t-ui-up-c 2811763 1 order configuration/kmat, wi th spring-cage connection macx mcr-ex-t-ui-up-sp-c 2924692 1 accessories description type order no. pcs. / pkt. operator interface for the configuration of compatible macx modules. ifs-op-unit 2811899 1 cradle unit, for snapping the operatin g and display unit onto the din rail ifs-op-cradle 2811886 1 programming adapter for ma cx mcr... devices. with usb interface for pro- gramming with the ifs-conf software ifs-usb-prog-adapter 2811271 1 cold junction compensation connector for thermocouples macx mcr-ex-cjc 2925002 1 for additional accessories, pl ease refer to the interface catalog from phoenix contact.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 6 4order key order key for temperature transducer macx-mcr-ex-t-ui-up(-sp)-c (standard configuration entered as an example) order no. safety integrity level (sil) sensor type connection method cold junction compensation measuring range: measuring unit output range factory calibration certificate = fcc start end 2811763 / on / pt100 / 4 / 0 / -50 / 150 / c / out02 / none 2811763  macx mcr-ex- t-ui-up-c on  active see below 2  2-wire 0  off, e.g. with rtd, r, potentiometer, mv see below see below c  c out15  0...5 ma none  without fcc f  f out16  0...10 ma none  not active o  out01  0...20 ma 3  3-wire p  %out15  0...5 ma yes  with fcc (a fee is charged) 2924692  macx mcr-ex- t-ui-up-sp-c v  mv out25  1...5 ma on only with output range = out02 1  on, e.g. with tc out26  2...10 ma 4  4-wire out02  4...20 ma out05  0...5 v yesplus  factory calibration certificate with 5 measuring points (a fee is charged) out03  0...10 v out06  1...5 v out04  2...10 v out13  -5...+5 v out14  -10...+10 v others freely configurable in the software smallest measuring range other setting options can be configured with the ifs-conf software. - freely configurable user characteristic with 30 interpolation points - output behavior in the event of a short circuit, sensor break, or overrange/underrange is freely configurable or can be set according to ne43 (standard configuration: ne43 upscale) - filter setting (standard configuration: 1) - restart after failsafe (standard configuration: on) - switching behavior: switching output ? (limit values, times, etc.) (standard configuration: off) resistance thermometers rtd others can be selected or are freely configured in the software. pt100  pt 100 acc. to iec/en 60751 -200 850 c 20 k pt200  pt 200 acc. to iec/en 60751 -200 850 c 20 k pt500  pt 500 acc. to iec/en 60751 -200 850 c 20 k pt1000  pt 1000 acc. to iec/en 60751 -200 850 c 20 k pt100s  pt 100 acc. to sama rc21-4-1966 -200 850 c 20 k pt1000s  pt 1000 acc. to sama rc21-4-1966 -200 850 c 20 k pt100g  pt 100 acc. to gost 6651 -200 850 c 20 k pt1000g  pt 1000 acc. to gost 6651 -200 850 c 20 k pt100j  pt 100 acc. to jis c1604/1997 -200 850 c 20 k pt1000j  pt 1000 acc. to jis c1604/1997 -200 850 c 20 k ni100  ni 100 acc. to din 43760/din iec 60751 -60 250 c 20 k ni1000  ni 1000 acc, to din 43760/din iec 60751 -60 250 c 20 k ni100s  ni 100 acc. to sama rc21-4-1966 -60 180 c 20 k ni1000s  ni 1000 acc. to sama rc21-4-1966 -60 180 c 20 k ni1000l  ni 1000 (landis & gyr) -50 160 c 20 k cu10  cu 10 acc. to sama rc21-4-1966 -70 500 c 100 k cu50  cu 50/cu 100 acc. to gost 6651 (  = 1.428) -50 200 c 100 k cu53  cu 53 acc. to gost 6651 (  = 1.426) -50 180 c 100 k kty81  kty81-110 (philips) -55 150 c 20 k kty84  kty84-130 (philips) -40 300 c 20 k thermocouples tc others can be selected in the software. b  acc. to iec/en 60584 (pt30rh-pt6rh) 500 1820 c 50 k e  acc. to iec/en 60584 (nicr-cuni) -230 1000 c 50 k j  acc. to iec/en 60584 (fe-cuni) -210 1200 c 50 k k  acc. to iec/en 60584 (nicr-ni) -250 1372 c 50 k n  acc. to iec/en 60584 (nicrsi-nisi) -250 1300 c 50 k r  acc. to iec/en 60584 (pt13rh-pt) -50 1768 c 50 k s  acc. to iec/en 60584 (pt10rh-pt) -50 1768 c 50 k t  acc. to iec/en 60584 (cu-cuni ) -200 400 c 50 k l  acc. to din 43760 (fe-cuni) -200 900 c 50 k u  acc. to din 43760 (cu-cuni) -200 600 c 50 k ca  c astm je988 (2002) 0 2315 c 50 k da  d astm je988 (2002) 0 2315 c 50 k a1g  a-1 gost 8.585-2001 0 2500 c 50 k a2g  a-2 gost 8.585-2001 0 1800 c 50 k a3g  a-3 gost 8.585-2001 0 1800 c 50 k mg  m gost 8.585-2001 -200 100 c 50 k lg  l gost 8.585-2001 -200 800 c 50 k remote resistance-type sensors r (2-, 3-, 4-wire) others can be selected in the software. res03  resistance 0...150 0 150 10% of the selected measuring range res05  resistance 0...600 0 600 res06  resistance 0...1200 0 1200 res09  resistance 0...6250 0 6250 res10  resistance 0...12,500 0 12500 res12  resistance 0...50,000 0 50000 potentiometers 3-wire others can be selected in the software. pot03  potentiometer 0...150 0 100 % 10% of the selected measuring range pot05  potentiometer 0...600 0 100 % pot06  potentiometer 0...1200 0 100 % pot09  potentiometer 0...6250 0 100 % pot10  potentiometer 0...12,500 0 100 % pot12  potentiometer 0...50,000 0 100 % voltage signals mv others can be selected in the software. v04  voltage (mv) -1000 +1000 mv 10% of nominal span 9 t [f] = C t [c] + 32 5 temperature conversion guide for c to f:
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 7 5 technical data input resistance thermometer pt, ni, cu sensors: 2-, 3-, 4-wire thermocouple sensor b, e, j, k, n, r, s, t, l, u, ca, da, a1g, a2g, a3g, mg, lg (see example, ?order key? on page 6) resistor 0 ? ... 50 k ? potentiometer 0 ? ... 50 k ? voltage -1000 mv ... 1000 mv output output signal 4 ma ... 20 ma with sil on (further output signals can be configured with sil off) maximum output signal voltage output current output 11 v 22 ma load voltage output current output 10 k ? 600 ? (at 20 ma) behavior in the event of a sensor error according to ne 43 (or freely definable) switching output contact type 1 pdt contact contact material agsno2, hard gold-plated maximum switching voltage 30 v ac (30 v dc) maximum switching current 0.5 a (30 v ac) / 1 a (30 v dc) cycles with ohmic load 1 x 10 5 general data supply voltage range 24 v ... 230 v ac/dc (-20%/+10%, 50/60 hz) current consumption < 50 ma (24 v dc) power consumption < 1.5 w temperature coefficient 0.01 %/k, maximum step response (0 ... 99 %) with sil without sil typ. 1000 ms typ. 700 ms transmission error, total < 0.1% (e.g., for pt100, 300 k span, 4 ... 20 ma) electrical isolation input/output input/power supply input/switching output output/power supply power supply/switching output 4-way, between input/output/power supply/switching output 375 v p (according to en 60079-11) 375 v p (according to en 60079-11) 375 v p (according to en 60079-11) 300 v rms reinforced insulation (according to en 61010/50178) 300 v rms reinforced insulation (according to en 61010/50178) ambient temperature operation storage/transport -20 c ... +65c -40 c ... +85c permissible humidity (operation ) 5% ... 95% (no condensation) shock 15g, iec 60068-2-27 vibration 5g, iec 60068-2-6 status indicators green led (supply voltage, pwr) red led, flashing (cable error, sensor error, err) red led (module error, err) yellow led (switching output)
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 8 housing material pa 66-fr color green degree of protection ip20 pollution degree 2 dimensions (width x height x depth) 17.5 x 99 x 114.5 mm inflammability class according to ul 94 v0 design terminal housing for mounting on din rails general data [...] conformance emc directive 2004/108/ec en 61326-1; en 61000-6-2 1 ; en 61000-6-4 ex directive (atex) en 60079-0, en 60079-11, en 60079-15, en 61241-0, en 61241-11 1 during the interference, there ca n possibly be small deviations. safety data according to atex for intrinsically safe circuits maximum voltage (uo) 6 v maximum current (io) 7.4 ma maximum power (po) 11 mw gas group ex ia iic ex ia iib maximum external inductance (lo) 100 mh 10 mh 1 mh 100 mh 10 mh 1 mh maximum external capacity (co) 1.3 f 1.7 f 2.6 f 6.8 f 9.2 f 15 f maximum internal inductance (ci) 44 nf 44 nf 44 nf 44 nf 44 nf 44 nf maximum internal inductance (li) negligible maximum voltage u m 253 v ac (125 v dc) approvals atex x ii (1)g [ex ia] iic; x ii (1)d [ex iad] x ii 3 g ex nac ic iic / iib / iia t4 x ibexu 10 atex 1044 ibexu 10 atex 1044 iecex approval [ex ia] iic; [ex iad]; ex nac ic iic t4 iecex ibe 10.0004x ul, usa/canada applied for functional safety (sil) can be used up to sil 2 connection data macx mcr-ex-t-ui-up conductor cross section solid (minimum/maximum) stranded (minimum/maximum) awg/kcmil (minimum/maximum) 0.2 mm 2 /2.5 mm 2 0.2 mm 2 /2.5 mm 2 24/14 stripping length 7 mm connection method plug-in screw connection tightening torque minimum 0.5 nm/maximum 0.6 nm connection data macx mcr-ex-t-ui-up-sp conductor cross section solid (minimum/maximum) stranded (minimum/maximum) awg/kcmil (minimum/maximum) 0.2 mm 2 /1.5 mm 2 0.2 mm 2 /1.5 mm 2 24/16 stripping length 8 mm connection method spring-cage connection
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 9 6 minimum span and measuring accuracies 6.1 pt and ni-rtd inputs minimum measuring span: with 10 ? r 0 < 100 ? : 100 k with 100 ? r 0 10 k ? : 20 k measuring accuracy: for 10 ? r 0 < 100 ? : 0.2 k x 100 ? / r 0 = 0.1% x (100 ? /r 0 ) x (200 k/measuring span) for 100 ? r 0 1 k ? : 0.2 k = 0.1% x (200 k/measuring span) for 1 k ? < r 0 10 k ? : 0.4 k = 0.1% x (400 k/measuring span) 6.2 cu-rtd inputs minimum measuring span: for 10 ? r 0 < 100 ? : 100 k for 100 ? r 0 10 k ? : 20 k measuring accuracy: for 10 ? r 0 < 100 ? : 0.5 k x 100 ? /r 0 = 0.1% x (100 ? /r 0 ) x (500 k/measuring span) for 100 ? r 0 1 k ? : 0.5 k = 0.1% x (500 k/measuring span) for 1 k ? < r 0 10 k ? : 1.0 k = 0.1% x (1000 k/measuring span) 6.3 ni1000 input (landis & gyr), kty 81-110, kty 84-130 (philips) minimum measuring span: 20 k measuring accuracy: 0.2 k 6.4 thermocouple input minimum measuring span with tc: 50 k measuring accuracy of the input with tc signals: tc type e, j, k, n, t, l, u, m, lr without cold junction error: 0.30 k tc types b, r, s, c, d, a1, a2, a3 without cold junction error: 0.50 k 6.5 cold junction error cold junction error: 1 k, maximum (with internal cold ju nction compensation). with external compensation it depends on the quality of the cold junction and the sensor used. 6.6 voltage signal input minimum measuring span: 10% of the nominal span of the respective range. measuring accuracy: 6.7 r transducers and resistors 50% of measuring range (nominal value of r transducer + lead resistance) measuring range minimum measuring span: 10% of the selected measuring range measuring accuracy: example: r transducer with nominal value: 1000 ? measuring range to be selected: 0 ... 1200 ? minimum measuring span: 10% of the selected measuring range = 120 ? measuring accuracy: 0.01% of the selected measuring range = 120 m ? -1000 ... 1000 mv : 0.01% (of measuring range) -500 ... 500 mv : 0.01% (of measuring range) -250 ... 250 mv : 0.01% (of measuring range) -125 ... 125 mv : 0.01% (of measuring range) -60 ... 60 mv : 0.01% (of measuring range) -30 ... 30 mv : 0.01% (of measuring range) -15 ... 15 mv : 0.01% (of measuring range) 0 ... 75 ? : 0.10% (of measuring range) 0 ... 150 ? : 0.05% (of measuring range) 0 ... 300 ? : 0.02% (of measuring range) 0 ... 600 ? : 0.01% (of measuring range) 0 ... 1200 ? : 0.01% (of measuring range) 0 ... 2400 ? : 0.01% (of measuring range) 0 ... 4800 ? : 0.01% (of measuring range) 0 ... 6250 ? : 0.02% (of measuring range) 0 ... 12500 ? : 0.02% (of measuring range) 0 ... 25000 ? : 0.02% (of measuring range) 0 ... 50000 ? : 0.02% (of measuring range)
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 10 6.8 potentiometer 50% of measuring range (nominal value of potentiometer + lead resistance) measuring range minimum measuring span: 10% of the selected measuring range measuring accuracy: example: potentiometer with nominal value: 1000 ? measuring range to be selected: 0 ... 1200 ? minimum measuring span: 10% of the selected measuring range = 120 ? measuring accuracy: 0.02% of the selected measuring range = 240 m ? 6.9 output signals analog output error 0... 75 ? : 0.10% (of measuring range) 0... 150 ? : 0.05% (of measuring range) 0... 300 ? : 0.02% (of measuring range) 0... 600 ? : 0.02% (of measuring range) 0 ... 1200 ? : 0.02% (of measuring range) 0 ... 2400 ? : 0.02% (of measuring range) 0 ... 4800 ? : 0.02% (of measuring range) 0 ... 6250 ? : 0.10% (of measuring range) 0 ... 12500 ? : 0.10% (of measuring range) 0 ... 25000 ? : 0.10% (of measuring range) 0 ... 50000 ? : 0.10% (of measuring range) 2 mv 0.01% at -10 ... 10 v 2 mv 0.02% at 0 ... 10 v 4 a 0.02% at 0 ... 20 ma
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 11 7 safety regulations and installation notes 7.1 installation and operation follow the installation instructions. when installing and operatin g the device, the applicable safety directives (including nati onal safety directives), acci- dent prevention regulations, as well as general technical regulations must be observed. for safety data, please refer to this data sheet and the cer- tificates (ec-type examination certificate, and other approv- als, if necessary). 7.2 safety regulations for installation in poten- tially explosive areas regulations for intrinsically safe circuits installation in zone 2 observe the specified conditions for use in potentially ex- plosive areas. warning: sensor does not conform to the specification make sure that the connected sensors are only used in the specified area (see ?order key? on page 6). warning: sensor wiring check the structure for functionally correct wiring (see ?basic circuit diagrams? on page 13). note: installation, operatio n, and maintenance may only be carried out by qualified specialist per- sonnel. note: do not open the device or making changes to it. do not repair the device yourself; replace it with an equivalent device. repairs may only be per- formed by the manufactur er. the manufacturer is not liable for damage resulting from violation. note: the ip20 degree of protection (iec 60529/en 60529) of the device is intended for use in a clean and dry environment. do not sub- ject the device to mechanical and/or thermal loads that exceed the specified limits. note: only specified devices from phoenix contact may be connected to the 12-pos. s- port interface. warning: explosion hazard the devices are approved for intrinsically safe (ex i) circuits up to zone 0 (gas) and ex zone 20 (dust). the technical safety values of the intrinsi- cally safe field devices have to match the specifi- cations of this package slip or otherwise the ec- type examination certificate. warning: explosion hazard if the device has been used in non-intrinsically safe circuits, it must not be used again in intrinsi- cally safe circuits. label the device clearly as be- ing not intrinsically safe. warning: explosion hazard if the device has been used in non-intrinsically safe circuits, it must not be used again in intrinsi- cally safe circuits. label the device clearly as be- ing not intrinsically safe. warning: explosion hazard the device is associated equipment of the ex-i protection type and is suitable for installation in zone 2. warning: explosion hazard install the device in a suitable, approved housing with a minimum of ip54 degree of protection . at the same time, observe iec 60079-14/en 60079-14 requirements. warning: explosion hazard disconnect the block power supply before : ? connecting or disconnecting cables of non- intrinsically safe circuits. warning: explosion hazard use only category 3g modules (atex 94/9/ec).
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 12 installation in areas with a danger of dust explosions connection to the intrinsicall y safe circuit in areas with a danger of dust explosions (zones 20, 21 and 22) is only permitted if the equipment connected to this circuit is ap- proved for this zone (e.g., category 1d, 2d or 3d). 7.3 use in safety-related applications (sil 2) when using the macx mcr-ex-t-ui-up... in safety-relat- ed applications, observe the inst ructions in the appendix, as the requirements differ for safety-related functions. . warning: explosion hazard the device must be stopped and immediately re- moved from the ex area if it is damaged, was sub- jected to an impermissible load, stored incorrectly or if it malfunctions. warning: explosion hazard the device is not designed for installation in ar- eas with a danger of dust explosions. warning: explosion hazard if, however, you wish to us e the device in zone 22, it must be installed in a housing that complies with iec/en 61241-1. in doing so, observe the maxi- mum surface temperatures. observe the require- ments of iec/en 61241-14. note: install the device in a suitable housing with ip54 protection. the switching output is no t intended for safety-re- lated applications.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 13 8 installation 8.1 basic circuit diagrams figure 1 sensor connection - resistance thermometers and potentiometers figure 2 sensor connection - thermocouples and mv sources 8.2 structure figure 3 structure macx mcr-ex-t-ui-up figure 4 structure macx mcr-ex-t-ui-up-sp 1 plug-in combicon connectors 2 s-port (12-pos. programming interface) 3 button s3 (up), adjustment and reset functions 4 button s2 (down), adjustment and reset functions 5 dip switch s1 for service mode 6 pwr led, green, power supply 7 dat led, green, no function at present 8 led err, red, module, cable and sensor error, under- range or overrange, service mode 9 do led, yellow, status of switching output note: electrostatic discharge! the device contains components that can be damaged or destroyed by electrostatic discharge. when handling the device, observe the neces- sary safety precautions against electrostatic dis- charge (esd) according to en 61340-5-1 and en 61340-5-2. take precautions against electrostatic discharge before opening the front cover. plc / dcs passive - + 3.3 3.2 - + 3.3 3.1 di 11 12 14 2.3 2.1 2.2 zone 2 in out power 24v ...230v ac/dc 3.3 3.1 1.2 3.2 1.1 2.3 2.1 2.2 1.3 4.3 4.1 4.2 5.3 5.1 5.2 c s-port gnd i u out out nc zone 0,1,2 zone 20,21,22 sensor / field 4.3 4.1 4.2 5.3 5.1 5.2 ? ? poti 4.3 4.1 4.2 ? rtd ? ? rtd1 rtd2 zone 0,1,2 zone 20,21,22 plc / dcs passive - + 3.3 3.2 - + 3.3 3.1 di 11 12 14 2.3 2.1 2.2 zone 2 in out power 24v ...230v ac/dc 3.3 3.1 1.2 3.2 1.1 2.3 2.1 2.2 1.3 4.3 4.1 4.2 5.3 5.1 5.2 c s-port gnd i u out out nc sensor / field 4.3 4.1 4.2 5.3 5.1 4.3 4.1 4.2 tc - + cj macx mcr-ex-cjc tc - + external cj mv 5.2 pw r dat err d o 1 4.2 5.2 2.2 3.2 4.3 5.3 2.3 3.3 macx mcr-ex-t-ui-up 32825 blomberg, germany ma cx m cr CexCtCuiCup ord. C no.: 2865654 exCtem perature transducer/ex Ctemperaturmessumform er s upp ly v olta ge : inpu t a na lo g Co ut d igita l Co u t m ax. v a lues 24v ... 230v ac/dc rtd, tc, mv, poti, r 0 C 20ma / 10v warning do not separate when energized and installed in zone 2 www.phoenixcontact.com see manual (C20%...+10%, 50hz/60hz) u = 253v m u = 253v m u = 6,0 v dc o t C20...+65c/ C4...+149f amb 0,5a (30v ac) / 1a (30v dc) i = 7,4 ma o p = 11 mw o u= 30v (zone 2) m p= 1,5w n out in g n d 1 4 1 1 1 2 n c i o u t u o u t 1.1 2.1 5.1 3.1 4.1 1.2 2.2 5.2 3.2 4.2 1.3 2.3 5.3 3.3 4.3 + s - p o r t c ? ? 3.1 3.2 3.3 2.1 2.2 2.3 1.1 1.2 1.3 1 2 3 5 4 7mm 0,5-0,6 nm 5-7 lb in macx mcr-... pw r d at err do 1 4 .2 5 .2 2 .2 3 .2 4 .3 5 .3 2 .3 3 .3 macx mcr-ex-t-ui-up-sp 3.1 3.2 3.3 1.1 1.2 1.3 2.1 2.2 2.3 32825 blomberg, germany m ac x m c r CexCtCuiCupCsp ord. Cno.: 2924689 exCtem perature transducer/ex Ctemperaturm essum form er supply voltage: input analogCout digitalCout max. values 24v ... 230v ac/dc rtd, tc, mv, poti, r 0 C 20ma / 10v warning do not separate when energized and installed in zone 2 www.phoenixcontact.com see m anu al (C20%...+10%, 50hz/60hz) u= 253v m u = 253v m u=6,0v dc o t C20...+65c/ C4...+149f amb 0,5a (30v ac) / 1a (30v dc) i=7,4ma o p = 11 mw o u= 30v (zone 2) m p= 1,5w n o u t in g n d 1 4 1 1 1 2 n c i out u out 1.1 2.1 5.1 3.1 4.1 1.2 2.2 5.2 3.2 4.2 1.3 2.3 5.3 3.3 4.3 + s - p o r t c ? ? 1 6 7 9 8 8mm macx mcr-...-sp
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 14 8.3 dimensions figure 5 dimensions (in mm) 8.4 mounting figure 6 mounting and removal ? mount the module on a 35 mm din rail according to en 60715. ? install the module in a suitable housing to meet the re- quirements for the protection class. ? before startup, check for corre ct function and wiring of the macx mcr-ex-t-ui-up..., in particular the wiring and marking of the intrin sically safe circuits. 8.5 connecting the cables ? screw terminal blocks (for macx mcr-ex-t-ui-up); litz wires provided with ferrules. permissible cable cross section: 0.2 mm 2 to 2.5 mm 2 ? spring-cage terminal blocks (for macx mcr-ex-t-ui-up-sp); litz wires provided with ferrules. permissible cable cross section: 0.2 mm 2 to 1.5 mm 2 ? install intrinsically safe and non-intrinsically safe cables separately. ? screw connection: ? insert the conductor into the corresponding con- nection terminal block. ? use a screwdriver to tighten the screw in the open- ing above the connection terminal block. ? spring-cage connection: ? insert a screwdriver into the opening above the connection terminal block. ? insert the conductor into the corresponding con- nection terminal block. 8.6 power supply the power supply has been designed as a wide range power supply (19.2 ... 253 v ac/dc). the module is sup- plied with voltage via connec tion terminal blocks 1.1 and 1.2. warning: explosion hazard if the module has been used in non-intrinsi- cally safe circuits, it must not be used again in intrinsically safe circuits. the module must be clearly labeled as non-intrin- sically safe. 99 1 7 ,5 114,5
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 15 8.7 sensor types the sensor types that can be us ed and their specific proper- ties can be found in section ?order key? on page 6 depending on the connection method, the following termi- nal points are to be connected for temperature measure- ment (see figure 1 on page 13). 8.7.1 thermocouple (tc) with internal cold junction compensation ? thermocouple connection: terminals 4.1 ?+?, 4.2 ?-? 8.7.2 thermocouple (tc) with external or without cold junction compensation ? thermocouple connection: terminals 5.1 ?+?, 5.2 ?-? 8.7.3 voltage input ? connection: terminals 5.1 ?+?, 5.2 ?-? 8.7.4 potentiometer ? connection: termin als 4.1, 4.2, 4.3 8.7.5 resistance thermometer (rtd) ? 2-wire connection method: terminals 4.2, 4.3 the cable resistance can be compensated with the help of the ifs-conf pc program, the ifs-op-unit opera- tor interface or in service mode (dip switch). ? 3-wire connection method: terminals 4.1, 4.2, 4.3 in the case of the 3-wire connection method, ensure that all three cable re sistances are the same. ? 4-wire connection method: terminals 4.2, 4.3, 5.1, 5.2 ? 2 x 2-wire connection method terminals rtd 1: 4.2, 4.3 terminals rtd 2: 5.1, 5.2 8.7.6 measuring resistances the terminal points 4.2 and 4.3 are used for measuring dif- fering resistances. 8.8 current output the current output can be fr eely configured between 0 and 20 ma. the minimum span is 4 ma. in safety-related appli- cations (sil = on), the output is fixed at 4 ...20 ma. ? connection: terminals 3.2 ?+?, 3.3 ?-? 8.9 voltage output the voltage output can be fr eely configured between -10 and +10 v. the minimum span is 2 v. ? connection: terminals 3.1 ?+?, 3.3 ?-? use the macx mcr-ex-cjc cold junction com- pensation connector provided (order no. 2925002). tc+cj: use the cold junc tion compensation con- nector provided at connection terminal blocks 4.1, 4.2 and 4.3. tc+cj external: use the external cold junction compensation sensor (e.g., pt100) at connection terminal blocks 4.2 and 4.3. rl 25 ? for each lead. up to 75 ? : rl 2.5 ? for each lead. up to 150 ? : rl 5 ? for each lead. up to 300 ? : rl 10 ? for each lead. the voltage output cannot be used for safety-re- lated applications (sil = on).
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 16 8.10 switching output switching output 1 has one pdt. the behavior of the switch- ing output can be selected . the switching points spl 1 and sph 2 can be configured across the entire sensor range: switching behavior of the switching output . switching behavior 0 switching output is permanently dropped. switching behavior 1 switching output is permanently picked up. switching behavior 2 switching output picks up when sph 2 is exceeded. switching behavior 3 switching output drops out when sph 2 is underrange. switching behavior 4 switching output picks up when spl 2 is exceeded and drops out when sph 1 is underrange (hysteresis). switching behavior 5 switching output drops out when spl 2 is exceeded and picks up when sph 1 is underrange (hysteresis). 1 0 1 0 sph 0 1 1 0 sph 0 1 spl sph 0 1 spl sph switching behavior 6 switching output picks up between spl 1 and sph 2 . switching behavior 7 switching output drops out between spl 1 and sph 2 . 1 spl = set point low (lower switching point) 2 sph = set point high (upper switching point) the switching output is no t intended for safety-re- lated applications. if only the switch ing output is to be used, the cur- rent output (connection terminal blocks 3.2 and 3.3) must be short circuited or subjected to a load. 1 0 spl sph 1 0 spl sph
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 17 8.11 switching output beha vior with manual ac- knowledgement (latching) 8.11.1 switching behavior (2): undertemperature limit ( sph) 8.11.2 (switching behavior (3): overtemperature limit ( sph) latching: no automatic restart after exceeding limit value (sph: set poin t high) or falling below limit value (spl: set point low). disable the option ?restart after fail safe? in the configuration software. normal operating state > sph step measure 1measured value > sph and module are acti- vated 2relay on 3measured value sph 4relay off 5measured value> sph 6 relay remains off (latches) until delay time has passed and then acknowledged manu- ally critical operating state sph step measure 1measured value sph and module are acti- vated 2relay off 3measured value > sph 4 relay remains off (latches) until delay time has passed and then acknowledged manu- ally sph 0 1 acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. normal operating state < sph step measure 1measured value < sph and module are acti- vated 2relay on 3measured value sph 4relay off 5measured value< sph 6 relay remains off (latches) until delay time has passed and then acknowledged manu- ally critical operating state sph step measure 1measured value sph and module are acti- vated 2relay off 3measured value < sph 4 relay remains off (latches) until delay time has passed and then acknowledged manu- ally 1 0 sph acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 18 8.11.3 switching behavior (4): undertemperature limit with hysteresis ( spl) 8.11.4 switching behavior (5 ): overtemperature limit with hysteresis ( sph) normal operating state > spl step measure 1measured value > spl and module are acti- vated 2relay on 3measured value spl 4relay off 5measured value> sph 6 relay remains off (latches) until delay time has passed and then acknowledged manu- ally critical operating state spl step measure 1measured value spl and module are acti- vated 2relay off 3measured value > sph 4 relay remains off (latches) until delay time has passed and then acknowledged manu- ally 0 1 spl sph acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. normal operating state < sph step measure 1measured value < sph and module are acti- vated 2relay on 3measured value sph 4relay off 5measured value< spl 6 relay remains off (latches) until delay time has passed and then acknowledged manu- ally critical operating state sph step measure 1measured value sph and module are acti- vated 2relay off 3measured value < spl 4 relay remains off (latches) until delay time has passed and then acknowledged manu- ally 0 1 spl sph acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 19 8.11.5 switching behavior (6): temperature range lim- it ( spl and sph) 8.11.6 switching behavior (7 ): temperature range lim- it ( spl and sph) normal operating state > spl and < sph step measure 1measured value > spl and < sph module are activated 2relay on 3measured value spl or sph 4relay off 5 measured value > spl or < sph 6 relay remains off (latches) until delay time has passed and then acknowledged manu- ally critical operating state spl and sph 1measured value a) spl and module are acti- vated b) sph and module are acti- vated 2relay off 3measured value a) > spl and < sph b) < sph and > spl 4 relay remains off (latches) until delay time has passed and then acknowledged manu- ally 1 0 spl sph acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. normal operating state < spl and > sph step measure 1measured value a) < spl and module are acti- vated b) > sph and module are acti- vated 2relay on 3measured value a) spl and sph b) sph and spl 4relay off 5 measured value < spl or > sph 6 relay remains off (latches) until delay time has passed and then acknowledged manu- ally critical operating state spl and sph step measure 1measured value spl and sph and mod- ule are activated 2relay off 3measured value < spl or > sph 4 relay remains off (latches) until delay time has passed and then acknowledged manu- ally 1 0 spl sph acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed. acknowledgement is only possible when there is no critical state anymore and the de- lay time has passed.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 20 8.12 monitoring function the temperature transducer is equipped with monitoring functions for the input and output range. input monitoring function the input monitoring function for line break and short circuit refers to the sensor connected to the input. when an error is detected, the output signal is set to the configured error value. in the case of rtd sensors and resistance-type sen- sors, short-circuit failures are detected resistance values < 1 ? . short circuits of thermocouples and mv sources cannot be detected, since 0 v can be a valid signal. on rtd sensors, resistance-type sensors and potentiome- ters, a line break is detected when the current flow through the sensor is faulty. as soon as the fault has been eliminated, the temperature transducer continues to perfor m its normal functions. (see ?led status indicators? on page 22, line faults) output monitoring function the current output can be monitored for line breaks and maximum load. this is activate d via the configuration. in safety-related applications (s il = on), the output monitor- ing is always active. the voltag e output is not monitored. as soon as the fault has been eliminated, th e temperature transducer continues to perfor m its normal functions. (see ?led status indicators? on page 22, line faults) 8.13 operating modes 8.13.1 sil on/sil off the temperature transducer can either be operated in sil on or sil off. the standard configuration is sil on with dip switch s1 set to the off position. with the order config- uration, customer-specific config urations can be selected in the order key (see ?order key? on page 6). 8.13.2 service mode service mode can be selected at any time via the ifs-op-unit operator interfac e and the configuration soft- ware, e.g., ifs-conf or via dip switch s1. if settings are changed during service mode and service mode is then exited, the temp erature transducer performs a warm start in order to apply the newly set values. if no changes are made, the transducer starts up in normal mea- suring mode without a warm start. the switching output switches according to its configuration. in service mode, it is also possible to simulate the output sig- nal independently of the input sign al (force). in this case, in safety-related applications the safety function of the device is deactivated and the initial va lue for the analog output sig- nal is 2 ma, which allows subsequent devices to detect the deviation from normal operation as a result of the measured value being underrange. during service mode, the switching output is deactivated and remains in its idle position. 9configuration figure 7 position of the dip switch and buttons if the configuration is modified using the ifs-op-unit operator in terface and pc-based software (e.g., ifs-conf) or via dip switch, the changes made must always be checked again and released before tran sfer to the temperature transducer. after the transfer, the new data in the temperature transducer is applied by means of activation and a warm start. warning: explosion hazard when configuring in zone 2, the pc used must be approved for use in zone 2. when a dip switch from s1-2 ... s1-8 (on) is switched on, the device is switched to service mode. the red err led flashes (1.2 hz) and a diagnostic i/o fault is displayed in the start screen. p w r d a t e r r d o 1 4 . 2 5 . 2 2 . 2 3 . 2 4 . 3 5 . 3 2 . 3 3 . 3 m a cx mcr -e x -t- u i- up ess um form er ut d i g i ta l C out ma x. v a l ues r m a / 10 v wa r nin g do n o t s e p a r ate when ene rg ize d an d in s talle d in z o ne 2 www. phoen ix contact . com see manua l u = 253 v m u = 6,0 v d c o t C 20 ...+ 65c / C 4 ...+ 1 4 9 f amb 0,5 a (30 v a c ) / 1 a (30 v dc) i = 7, 4 m a o p = 11 m w o u = 30 v ( z one 2) m ou t in g n d 1 4 11 12 n c i o u t u o u t 1 . 1 2 . 1 5 . 1 3 . 1 4 . 1 1 . 2 2 . 2 5 . 2 3 . 2 4 . 2 1 . 3 2 . 3 5 . 3 3 . 3 4 . 3 + s - p o r t c ? s1 s2 s3
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 21 9.1 delivered state/standard configuration 9.2 zero adjust, adjustment via buttons s2 and s3 (only possible with sil off) ? set the adjustment by settin g dip switch s1-2 to on. ? observe the analog output and set it with button s2 (de- scending value) or s3 (ascending value) or press the buttons s2 and s3 simultaneously time for > 3 seconds to reset the cable compensation. ? save the set value by settin g dip switch s1-2 back to off. 9.3 span adjust, adjustment via buttons 2 and 4 (only possible with sil off) ? set the adjustment by settin g dip switch s1-3 to on. ? observe the analog output and set it with button s2 (de- scending value) or s3 (ascending value) or press the buttons s2 and s3 simultaneously time for > 3 seconds to reset the cable compensation. ? save the set value by settin g dip switch s1-3 back to off. ? pressing buttons s2 and s3 simultaneously for > 3 sec- onds resets the adjustment. 9.4 force output ? set the adjustment by settin g dip switch s1-4 to on. ? observe the analog output and set with the s2 (de- scending value) or s3 (ascending value) button. ? the specification/simulation is reset and ended by set- ting dip switch s1-4 back to off. 9.5 cable compensation, 2-wire rtd or rtd 1 with 2 x rtd ? set the cable compensation rtd 1 via dip switches s1-1 to off and s1-5 to on. ? short circuit the sensor. ? apply the current measured value as the cable resis- tance by pressing the s2 button. ? save the set value by settin g dip switch s1-5 back to off. pressing buttons s2 and s3 simultaneously for > 3 seconds resets the cable compensation. switch position dip-s1 12345678 offoffoffoffoffoffoffoff switch position dip-s1 12345678 off on off off off off off off switch position dip-s1 12345678 off off on off off off off off when sil is activated, the analog output starts at 2 ma and the switching output is deactivated. switch position dip-s1 12345678 off off off on off off off off switch position dip-s1 12345678 off off off off on off off off
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 22 9.6 cable compensation rtd 2 with 2 x rtd or tc with external cold junction compensa- tion (tc + cj external) ? set the cable compensation rtd 2 via dip switches s1-1 to on and s1-5 to on. ? short circuit the sensor. ? apply the current measured value as the cable resis- tance by pressing the s2 button. ? save the set value by settin g dip switches s1-1 and s1- 5 back to off. pressing buttons s2 and s3 simultaneously for > 3 seconds resets the cable compensation. 9.7 automatic potentiometer adjustment (teach-in) ? set the teach-in by settin g dip switch s1-6 to on. ? set potentiometer to start of range. ? press the s2 button. ? set potentiometer to end of range. ? press the s3 button. ? save the new measuring range by setting dip switch s1-6 back to off. pressing buttons s2 and s3 simultaneously for > 3 seconds resets both values. 9.8 manual acknowledg ement of switching outputs (latch function) ? set manual acknowledgment by setting dip switch s1- 7 to on. ? press buttons s2 and s3 simultaneously for > 3 sec- onds. ? reset dip switch s1-7 to off. 9.9 led status indicators figure 8 led status indicators switch position dip-s1 12345678 on off off off on off off off switch position dip-s1 12345678 offoffoffoffoff on off off switch position dip-s1 12345678 offoffoffoffoffoff on off no. led color description 6 pwr green supply voltage on indicates the readiness for opera- tion of the temperature trans- ducer if supply voltage is avail- able. the temperature transducer is configured without device supply via programming adapter ifs- usb-prog-adapter. 7 dat green no function at present 8 err red error on module error flashing (1.2 hz) service mode active flashing (2.4 hz) line fault 9 do yellow switching output 1 on switching output active p w r d at e r r do 1 4 . 2 5 . 2 2 . 2 3 . 2 4 . 3 5 . 3 2 . 3 3 . 3 m a cx mcr -e x -t- u i- up - sp 3 . 1 3 . 2 3 . 3 1 . 1 1 . 2 1 . 3 2 . 1 2 . 2 2 . 3 32825 b l omberg, germany m a c x m c r C ex C t C u i C up C sp ord . C n o .: 292 4 689 ex C t em perature t ransducer /ex C t em pe ra turm e ssum form er supp l y v o l tage : i nput a na l og C out d i g i ta l C out ma x. v a l ues 2 4v ... 230 v a c / dc r t d, t c, m v , pot i , r 0 C 20m a / 10 v wa r nin g do n o t s e p a r ate when ene rg ize d an d in s talle d in z o ne 2 www. phoen ix contact . com s e e m a n u a l ( C 20% ...+ 10%, 50 hz/ 60 hz ) u = 253 v m u = 253 v m u = 6,0 v dc o t C 20 ...+ 65c / C 4 ...+ 1 4 9 f am b 0,5 a (30 v a c) / 1 a (30 v dc) i = 7, 4 m a o p = 11 m w o u = 30 v ( z one 2) m p = 1,5 w n ou t in g n d 1 4 11 12 n c i o u t u o u t 1 . 1 2 . 1 5 . 1 3 . 1 4 . 1 1 . 2 2 . 2 5 . 2 3 . 2 4 . 2 1 . 3 2 . 3 5 . 3 3 . 3 4 . 3 + s - p o r t c ? ? 6 7 9 8
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 23 10 password the device is protected by means of a four-digit password set in the factory in order to prevent impermissible changes to the configuration. default setting: 1111 if, however, only data from the device is to be displayed or the device is to be used in non-safety-related applications, the password can be deactivated. setting: 0000 the device can be accessed either via the ifs-op-unit (order no.: 2811899) or via a service pc with connected programming adapter ifs-usb-prog-adapter (order no.: 2811271) and the ifs-conf configuration software. 11 flow chart, operator interface configuration with the ifs-op-unit if you wish to use the macx mcr-ex-t-ui-up in combina- tion with the ifs-op-unit and with the ifs-op-cradle, the various operating function s that can be selected are shown in the display. example: display of sil on example: display of sil off for safety-related applic ations, the password set in the factory must always be changed. if the password is lost, it is not possible to reset it. in this case, please contact phoenix contact. further information on configuration with the ifs-op-unit or the ifs-conf configuration software can be found in the relevant user manu- al. warning: if functional safety is activated by a reconfiguration or changes are made to the active functional safety configuration, the rules under installation and startup must be observed. warning: limitations on safety-related ap- plications only 4 ... 20 ma, limited programming of output current in the event of line faults (2 ma i out 3.6 ma or i out 21 ma) warning: once new configuration data has been written, the device performs a warm start that changes the properties of the device. the fol- lowing control device must be adapted to these modifications. note: transfer and activate the configuration af- ter the password has been changed. when active, the sil functionality is displayed in the start screen. for safety reasons, the sil function cannot be switched on again via the ifs-op-unit operator interface. sil can be switched off/deactivated via the sil off menu item. to reactivate/switch on the sil function, pc- based configuration softwa re, e.g., ifs-conf is required. if no input is entered for five minutes during con- figuration, the configurat ion is ended and any un- saved data will be lost. input 1 sil ok input 1 ok
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 24 11.1 menu structure onl y 2 x r t d2 onl y 2 x r t d2 and di ff erential meas u rement o k / e sc o k / e sc o k o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc o k / e sc settin g s con f i gu re i n pu t i n pu t con f o u t pu t e rr .h andl . ser v i c e sa v e password t rans f er sa v e con f password ac ti v ate b a ckup o u t p. con f b a ck li gh t cj on / o ff l an gu a g e cj v al u e t em p- unit f ilter 2w - com p. c1 2w - com p. c2 restore o k / e sc o k / e sc swit ch swit ch 1 on - dela y o ff- dela y ack nowled . l inebrea k s h orted i n pu t 1 i n pu t 2 i n pu t di ff o u t pu t start s c reen settin g s mod u l - in f ormation dia g nosti c c h e ck b/lb reset cor . restart mod u l c h an g e pw reset s il o ff reset sw1
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 25 11.2 key for start screen display of input and outp ut signals, module and diagnostic information. 11.3 key for settings - menu 11.4 key for settings - configure display of the actual value of input 1 display of the actual value of inpu t 2, only if a second rtd is conf igured with the 2-wire connection method. display of the actual value of th e differential measurement with 2 x rtd with the 2-wire connection method. display of the actual value of the analog output display of module information (order design ation, firmware version, config version) module diagnostics (simulation, module error, i/o error) the active configuration is read out from the module. setting for the background illu mination (on, off, autodim) setting for the menu language (english, german) configuration of input, output, fault behavior and switching outputs i n pu t 1 i n pu t 2 i n pu t di ff o u t pu t mod u l - in f ormation dia g nosti c settin g s b a ck li gh t l an gu a g e con f i gu re
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 26 11.5 key for settings - service 11.6 key for settings - save access to the menu items of the service area input of a 4-digit numeric password in order to open the service area (if the password is 0000, the pa ssword prompt is switched off) access to the menu items for the backup and restore functionality of the module configuration resets switching output 1 when it is snapped on (latching behavior) changes the set password (change only becomes effective when the configuration has been transmitted to the module and acti- vated) changes the setting from sil on to sil off. resets the ifs-op-unit and the connected module. saves the active configuration of the connected, compatible module in the ifs-op-unit operator inter- face (copy function) transmits the saved module configur ation from the internal memory of the ifs-op-unit operator inter- face to the connected module (copy function). access to the menu items for the transmission and activation of the module configuration transmits the configuration from the ifs-op-uni t operator interface to the connected module input of a 4-digit numeric password in order to transmit the configuration (if the password is 0000, the passw ord prompt is switched off). activation of the module configuration (yes/no) ser v i c e password sa v e con f reset sw1 c h an g e pw s il o ff note: it is only possible to switch on the sil function via pc-based configuration software, e.g., ifs-conf. reset b a ckup restore then activate the configuration by sele cting yes in the activate menu item. sa v e t rans f er password ac ti v ate following activation, the modu le performs a warm start.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 27 11.7 key for input 11.7.1 key for input configuration (analog input) configuration selection, input configuration access to the menu items for th e configuration of the input (see ?key for input configuration (analog input)? on page 27) i n pu t setting for the dependent parameters of the input mode , sensor type, start and en d of range, associated inputs, switching behavior, switching points cold junction compensation with tc + cj and tc + cj ext. (on, off) correction of the cold junction value with cj = on, specification of the cold junction value with cj = off (-20 ... 65 k). setting for the temperature unit (c, f) setting for the filter factor (1 ... 10) setting for the cable resistance for rtd 2-wire connection method, channel 1 (0 ... 50 ? ). setting for the cable resistance for rtd 2-wire connection method, channel 2 (0 ... 50 ? ). i n pu t con f cj on / o ff cj v al u e t em p- unit f ilter 2w - com p. c1 2w - com p. c2 i n pu t con f di ff r e nd rstart i n1 con . i n a o con . i n sw1 mode sw1 sp l sw1 sp h sw1 r e nd i n2 di ff eren c e sensort yp e cj sensor di ff rstart r e nd i n1 rstart i n2 r t d b ase cj r t d b ase v arialble r t d b ase v arialble r t d b ase di ff eren c e e sc o k o k o k o k o k o k o k o k o k o k o k o k o k o k o k o k o k y y y n n n i n pu t con f i gu ration mode = 2x r t d2 mode = t c + cj extern i n pu t con f input conf esc ok
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 28 setting for the sensor mode (rtd4, rtd3, rtd2, 2 x rtd2, tc + cj , tc + cj ext., potentiometer, mv). setting for the sensor type depending on sensor mode (pt, ni, cu, kty..., user, for more see ?order key? on page 6). rtd basic resistance for sensor type s with a variable basic resistance (e.g., when 100 is selected, the basic resistance is 100 ? ) start of range for input 1 depending on sensor type, e.g., -50c (c, f, ? , %, mv). end of range for input 1 depending on sensor type, e.g., 150c (c, f, ? , %, mv) start of range for input 2 depending on sensor type and only for 2 x rtd with 2-wire connection method, e.g., -50c (c, f, ? ). end of range for input 2 depending on sensor type an d only for 2 x rtd with 2-wire connection method, e.g., 150c (c, f, ? ) setting for the differential measurement only for 2 x rtd with 2-wire connection method and not resis- tance (off, differential, absolu te value differential) start of range for differential, only with differ ential and absolute value differential (c, f) end of range for differential, on ly with differential and absolu te value differential (c, f) sensor type of the cold junction, only with tc + cj ext. rtd basic resistance of the cold junction, only with tc + cj ext. associated input of the analog output (input 1, input 2, differential), appears only in sensor mode 2 x rtd2 (2 x rtd 2-wire connection method) associated input of the switching outp ut (input 1, input 2, differential), appears only in sensor mode 2 x rtd2 (2 x rtd 2-wire connection method) mode of switching output (0 ... 7) (see ?switching output? on page 16) setpoint low of switching output (appears only if mode > 3) (see ?switching output? on page 16). setpoint high of switching output (appears only if mode > 1) (see ?switching output? on page 16) i n pu t con f sensort yp e r t d b ase rstart i n1 r e nd i n1 rstart i n2 r e nd i n2 di ff eren c e di ff rstart di ff r e nd cj sensor cj r t d b ase con . i n a o con . i n sw1 mode sw1 sp l sw1 sp h sw1
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 29 11.8 key for output 11.8.1 key for output configuration (analog output) configuration selection, output configuration access to the menu items for th e configuration of the output (see ?key for output configuration (analog output)? on page 29) setting for the dependent parameters of the analog outp ut ? mode, start and end of range, display of cor- rection values, fault behavior (or, ur, lb, ks) monitoring of output load/short circuit ( yes /no), only configurable with sil = off resets the correction values of the output o u t pu t o u t p. con f c h e ck b/lb reset cor . o v erran g e underran g e ran g estart ran g e e nd l inebrea k corr . start s h orted corr . e nd o k / e sc o k o k o k o k o k o k o k o u t pu t con f i gu ration o u t p. con f o u t p. con f outp. conf esc ok start of range for output ? setting only possible with sil = off, 4 ma (0 ... 20 ma, -10 ... 10 v) end of range for output ? setting only possible with sil = off, 20 ma (0 ... 20 ma, -10 ... 10 v) display of the start correction va lue for the analog output (ma, v) display of the end correction valu e for the analog output (ma, v) analog output value when overrange ne43 upsc. / ne43 downsc. (configurable for fault behavior = freely definable) analog output value for underrange ne43 upsc. / ne43 downsc. (configurable for fault behavior = freely definable) analog output value in the event of line break ne43 upsc. / ne43 downsc. (configurable for fault behavior = freely definable) analog output value in the even t of a short circuit on the line ne43 upsc. / ne43 downsc. (configurable for fault behavior = freely definable) ran g estart ran g e e nd corr . start corr .e nd o v erran g e underran g e l inebrea k s h orted
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 30 11.9 key for error handling 11.10 key for switch 12 ifs-op-unit operator interface error codes the following error codes are sh own directly in the display of the ifs-op-unit operator interface when they occur. setting for the fault behavior (ne43 incr easing, ne43 decreasing, freely definable) access to the menu items for setting the switching output access to the menu items for setting the switching output setting for the switch-on delay for the switching output (0 ... 10 s) setting for the off delay for the switching output (0 ... 10 s) manually acknowledge switchin g output (latching) (yes/ no ) behavior for switching output in th e event of an error - line break ( on , off, no response) behavior for switching output in the event of an error - short circuit (on, off, no response). e rr .h andl . swit ch swit ch 1 on - dela y o ff- dela y ack nowled . l inebrea k s h orted error code description error 0 copy error module type in the ifs-op-unit is differ- ent from the connected module. error 1,2,3 checksum error please contact phoenix contact.
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 31 13 configuration with the service pc when making changes to the configuration data, use the ifs-conf software (free download: www.phoenixcontact.net/catalog ). ? connect the device and pc with the help of the ifs- usb-prog-adapter programming adapter (order no. 2811271). figure 9 ifs-usb-prog-adapter changes to the configuration and parameterization data can be made during operation with a connected ex measuring circuit as well as in a disconnected state. 13.1 system requirements ? ibm pc or compatible computer with 400 mhz or higher with at least 256 mbyte ram ? at least 15 mbyte available hard disk space ? free usb interface, at least usb 1.1. ? screen resolution of 1024 x 768 pixels ? windows 2000 sp4, windows xp sp2 13.2 configuring the user characteristic curve the user characteristic curve is created with the pc-based ifs-conf software and stored in the temperature trans- ducer. 14 comparison of safety data safety data for the the values for u o , i o , p o , l o a nd c o can be found under ?safety data according to atex for intrinsically safe circuits? on page 8. requirements for intrinsic safety (simple circuits): u i u o i i i o p i p o l i + l c l o c i + c c c o (l c and c c depend on the cables/lines used). information on configurat ion, parameterization and service options (e.g., online monitoring) and their execution can be foun d in the online help of the software and in the associated user manuals of the dtms (device type manager). the drivers for the ifs-usb-prog-adapter usb programming adapter are installed automat- ically. pwr d at e rr do 1 4 . 2 5 . 2 2 . 2 3 . 2 4 . 3 5 . 3 2 . 3 3 . 3 m a cx mcr -e x -t- u i- up 3 2 8 2 5 b l o m b e rg , g e rm a n y m a c x m cr C ex C t C u i C up ord . C n o .: 286565 4 ex C t emperature t ransducer /ex C t emperaturmessumformer supp l y v o l tage : i nput a na l og C out d i g i ta l C out ma x. v a l ues 2 4v ... 2 3 0 v a c / d c r t d , t c , m v , p o t i , r 0 C 2 0 m a / 1 0 v wa r nin g do n o t s e p a r ate w hen ene rg ize d an d in s talle d in z o ne 2 www. phoen ix contact . com see m anua l ( C 20% ...+ 10% , 50 h z/ 60 h z ) u = 253 v m u = 25 3 v m u = 6,0 v d c o t C 20 ...+ 65c / C 4 ...+ 1 4 9 f amb 0,5 a (30 v a c ) / 1 a (30 v d c ) i = 7, 4 m a o p = 11 m w o u = 30 v ( z one 2) m p = 1,5 w n o u t in g n d 1 4 1 1 1 2 n c i o u t u o u t 1 . 1 2 . 1 5 . 1 3 . 1 4 . 1 1 . 2 2 . 2 5 . 2 3 . 2 4 . 2 1 . 3 2 . 3 5 . 3 3 . 3 4 . 3 + s - por t c ? ? 3 . 1 3 . 2 3 . 3 2 . 1 2 . 2 2 . 3 1 . 1 1 . 2 1 . 3 freely configurable user characteristic curve for individual adaptation of resistance temperature detectors (rtd) and thermocouples (tc). the user characteristic cu rve is either selected with the ifs-conf or with the ifs-op-unit soft- ware. warning: explosion hazard compare the safety data before connecting a de- vice located in the intrinsically safe area to the macx mcr-ex-t-ui-up.... field devices: u i, i i, p i , l i , c i temperature transducers: u o, i o, p o , l o , c o
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 32 15 application examples 15.1 current output connection example 1: connection example 2: connection example 3: 15.2 voltage output connection example: input: 4-wire rtd output: current output (4 ... 20 ma) on passive safe controller input: thermocouple with internal cold junction compensation output: current output (4 ... 20 ma) on passive safe controller plc / dcs in out power 24v ...230v ac/dc 3.3 3.1 1.2 3.2 1.1 2.3 2.1 2.2 1.3 4.3 4.1 4.2 5.3 5.1 5.2 c s-port gnd i u out out nc ? sensor / field zone 0,1,2 zone 20,21,22 use the macx mcr-ex-cjc cold junction compensation connector provided (order no. 2925002). plc / dcs zone 0,1,2 zone 20,21,22 in out power 24v ...230v ac/dc 3.3 3.1 1.2 3.2 1.1 2.3 2.1 2.2 1.3 4.3 4.1 4.2 5.3 5.1 5.2 c s-port gnd i u out out nc sensor / field tc - + input: thermocouple with external or without in- ternal cold junction compensation or volt- age input output: current output (4 ... 20 ma) on passive safe controller input: potentiometer output: voltage output (-10 ... 10 v) on passive controller plc / dcs zone 0,1,2 zone 20,21,22 in out power 24v ...230v ac/dc 3.3 3.1 1.2 3.2 1.1 2.3 2.1 2.2 1.3 4.3 4.1 4.2 5.3 5.1 5.2 c s-port gnd i u out out nc sensor / field tc - + = mv p l c / dcs i n ou t power 24 v ... 230 v a c / dc 3 . 3 3 . 1 1 . 2 3 . 2 1 . 1 2 . 3 2 . 1 2 . 2 1 . 3 4 . 3 4 . 1 4 . 2 5 . 3 5 . 1 5 . 2 c s - por t gnd i u ou t ou t n c sensor / f ield poti z one 0,1,2 z one 20,21,22
macx mcr-ex-t-ui-up... 104601_en_04 phoenix contact 33 15.3 switching output connection example: input: 3-wire rtd output: voltage output (-10 ... 10 v) on passive controller switching output: dependent on selected switching behavior p l c / dcs i n ou t power 24 v ... 230 v a c / dc 3 . 3 3 . 1 1 . 2 3 . 2 1 . 1 2 . 3 2 . 1 2 . 2 1 . 3 4 . 3 4 . 1 4 . 2 5 . 3 5 . 1 5 . 2 c s - por t gnd i 24 v ou t ou t n c sensor / f ield ? d i z one 0,1,2 z one 20,21,22
appendix - safety-related applications (sil 2) en version 04 phoenix contact a-1 appendix a1 safety-related applications (sil 2) valid hardware and firmware versions sil regulations apply to the following modules: the safety-related temperat ure transducers listed above from the macx mcr(-ex)-t-... series have been evaluated by exida certification s.a. via a full assessment in accor - dance with iec 61508 ed.1.0 to sil 2. certificate number: phoenix contact 100134c p0019 c001. a1.1 safety function and safety requirements the safety-related measuring transducers are used for the acquisition of a sensor signal (rtd, tc sensors, resistance- type sensors, mv sources), that is converted into a scaled signal and from which a standardized ?life zero? current sig - nal is generated. the entire co nversion is continuously mon - itored to a maximum transmissi on error of 5%. in the event of greater deviations, the device switches to the safe state. the safe state is an output sign al of either < 3.6 ma or > 21 ma. with the rel versions, an additional signal is generated, which is compared with up to two specified switching thresh - olds. when the first threshold is reached, the safety relay is switched on without confirmation contact and when the sec - ond threshold is reached, it is switched off. depending on the application, the safety for the switching output is imple - mented by either the series or parallel connection of relays 2 and 3, a fuse connected in series, and by monitoring the calculated switching value. in the event of deviations of more than 5%, the device swit ches to the safe state. the safe state in this case is an uncontrolled relay. the hardware is also continuous ly monitored. if an internal failure is detected, the measuring transducer also switches to the safe state (current outp ut < 3.6 ma or > 21 ma or un - controlled relay). the transition to the safe state always takes place within the internal failure detection time of 50 s. the measuring transducer is re leased (restarted) by switch - ing off the supply voltage and swit ching it back on again, by resetting the transducer via the serial interface, or by activat - ing the ?restart? option during configuration. the integrated startup tests are then performed. if the error is still present, it will be detected during these te sts. if it is still present, the measuring transducer switches back to the safe state. in addition to the safety functi ons, there are also monitoring functions for the input and the current output. evaluation failures which are detected in the measuring transducer and to which the transducer re sponds by switching to the safe state are safe failures ( s). failures where the measuring tr ansducer does not follow a change of input signal or generates an output signal that de - viates from the intended valu e by more than 5%, are eval - uated as dangerous failures ( d). both safe ( s) and dangerous ( d) failures can be detected by diagnostic measures. detected dangerous failures ( dd) are handled in the same way as safe failures. the monitoring functions refer to events whose cause is detected and reported outside of the device. note: only those devices with sil designa - tion and device firmware with revision 0.92 or higher are certified for sil 2. designation order no. standard configuration macx mcr-t-ui-up 28 11 394 macx mcr-t-ui-up-sp 28 11 860 macx mcr-t-uirel-up 28 11 378 macx mcr-t-uirel-up-sp 28 11 828 macx mcr-ex-t-ui-up 28 65 654 macx mcr-ex-t-ui-up-sp 29 24 689 macx mcr-ex-t-uirel-up 28 65 751 macx mcr-ex-t-uirel-up-sp 29 24 799 order configuration macx mcr-t-ui-up-c 28 11 873 macx mcr-t-ui-up-sp-c 28 11 970 macx mcr-t-uirel-up-c 28 11 514 macx mcr-t-uirel-up-sp-c 28 11 831 macx mcr-ex-t-ui-up-c 28 11 763 macx mcr-ex-t-ui-up-sp-c 29 24 692 macx mcr-ex-t-uirel-up-c 28 65 722 macx mcr-ex-t-uirel-up-sp-c 29 24 809 note: the evaluation unit following the measur - ing transducer (e.g., safety-related plc) must recognize these states and correspondingly con - trol the actuator as the final link in the safety chain.
appendix - safety-related applications (sil 2) en version 04 phoenix contact a-2 summary: together with the actual signal transmission, continuous checks and diagnostic functions are performed in the mea - suring transducers in order to detect faulty behavior. the internal failure monitoring time (diagnostics test in - terval) is the time taken to carry out and repeat these tests in full. random hardware faults are detected during this time. the internal failure monitoring time is 50 seconds. a1.2 safety integrity requirements a1.2.1 failure rates: ma cx mcr(-ex)-t-uirel-up (-sp)(-c) ? type b device (according to en 61508-2) ? safety integrity level (sil) 2 ?hft = 0 ? 1oo1d architecture the total failure rate is: 1.34 * 10 -6 the mtbf (mean time between failures) is therefore 85 years. the probability of a dangerous failure per hour for ?continu - ous demand? mode and the aver age probability of failure of the specified function for ?low demand? mode are deter - mined from the error rate: pfd avg values pfh* = 4.3 * 10 -8 /h the calculation is performed assuming a checking interval (t proof ) of 1 year and a repair time (mttr) of 24 hours, a test coverage (cpt) of 95% and a life time (lt) of 10 years. on the basis of the value dete rmined for the average proba - bility of failure pfd avg , the checking interval can be in - creased to up to 5 years. the values are valid under the following conditions: ? the failure rates of the components used remain con - stant throughout the period of use. ? the propagation of failures by the device in the system is not taken into consideration. ? the repair time (replacement) is 24 hours. ? the failure rates of the external power supply unit are not taken into consideration. ? the average temperature at which the device is to be used is 40c. in this case, normal industrial conditions are assumed. ? the specified failure rates are based on an average am - bient temperature of 40c . for an average ambient temperature of 60c, the failure rates must be multiplied by factor 2.5. factor 2.5 is based on guide values. safety/monitor - ing function output sig - nal range safe state reason safety function 4 ... 20 ma < 3.6 ma; or > 21 ma relay is not con - trolled deviation > 5% input monitoring 4 ... 20 ma 2 - 3.6 ma; > 21 ma line fault input output monitoring 4 ... 20 ma = 0 ma line fault out - put as a result of the multiple connection options, only two device types ar e considered in the con- figurations for ?rtd 3-wire? or ?mv? in the follow- ing. they represent all configurations with a variable resistance at th e input terminals or volt- age or thermocouple inputs and always indicate the most conservative case. the two device types are: 1. macx mcr(-ex)-t-ui-up(-sp)(-c) 2. macx mcr(-ex)-t-uirel-up(-sp)(-c) fit (failure in time) 1 fit is 1 failure in 10 9 hours input: rtd 3-wire connection method output: switching output 2 and 3 (redundant) sd su dd du sff dc d 0 2.34 * 10 -7 5.43* 10 -7 0.43 * 10 -7 94% 92 % 0 fit 234 fit 543 fit 43 fit t[proof] = 1 year 2 years 5 years pfd avg = 2.88 * 10 -4 4.67 * 10 -4 1.01 * 10 -3
appendix - safety-related applications (sil 2) en version 04 phoenix contact a-3 1.2.2 failure rates: macx mcr(-ex)-t-uirel-up (-sp)(-c) ? type b device (according to en 61508-2) ? safety integrity level (sil) 2 ?hft = 0 ? 1oo1d architecture the total failure rate is: 1.34 * 10 -6 the mtbf (mean time between failures) is therefore 85 years. the probability of a dangerous failure per hour for ?continu - ous demand? mode and the aver age probability of failure of the specified function for ?low demand? mode are deter - mined from the error rate: pfd avg values pfh* = 5.6 * 10 -8 /h the calculation is performed a ssuming a checking interval (t proof ) of 1 year and a repair time (mttr) of 24 hours, a test coverage (cpt) of 95% and a life time (lt) of 10 years. on the basis of the value dete rmined for the average proba - bility of failure pfd avg , the checking interval can be in - creased to up to 5 yearsif the percentage of the device for the entire loop is assumed at 10%. the values are valid under the following conditions: ? the failure rates of the components used remain con - stant throughout the period of use. ? the propagation of failures by the device in the system is not taken into consideration. ? the repair time (replacement) is eight hours. ? the failure rates of the external power supply unit are not taken into consideration. ? the average temperature at which the device is to be used is 40c. in this case, normal industrial conditions are assumed. ? the specified failure rates are based on an average am - bient temperature of 40c . for an average ambient temperature of 60c, the failure rates must be multiplied by factor 2.5. factor 2.5 is based on guide values. 1.2.3 failure rates: macx mcr(-ex)-t-ui-up(-sp) (-c) ? type b device (according to en 61508-2) ? safety integrity level (sil) 2 ?hft = 0 ? 1oo1d architecture the total failure rate is: 1.18 * 10 -6 the mtbf (mean time between failures) is therefore 97 years. the probability of a dangerous failure per hour for ?continu - ous demand? mode and the aver age probability of failure of the specified function for ?low demand? mode are deter - mined from the error rate: pfd avg values pfh* = 4.3 * 10 -8 /h the calculation is performed assuming a checking interval (t proof ) of 1 year and a repair time (mttr) of 24 hours, a test coverage (cpt) of 95% and a life time (lt) of 10 years. on the basis of the value dete rmined for the average proba - bility of failure pfd avg , the checking interval can be in - creased to up to 5 years. the values are valid under the following conditions: ? the failure rates of the components used remain con - stant throughout the period of use. ? the propagation of failures by the device in the system is not taken into consideration. input: voltage input mv output: switching output 2 and 3 (redundant) sd su dd du sff dc d 0 2.38 * 10 -7 5.22* 10 -7 0.56 * 10 -7 93% 90% 0 fit 238 fit 522 fit 56 fit t[proof] = 1 year 2 years 5 years pfd avg = 3.67 * 10 -4 5.99 * 10 -4 1.30 * 10 -3 input: rtd 3-wire connection method output: 4 ... 20 ma (current output) sd su dd du sff dc d 0 0 8.05* 10 -7 0.43 * 10 -7 94% 94% 0 fit 0 fit 805 fit 43 fit t[proof] = 1 year 2 years 5 years pfd avg = 2.95 * 10 -4 4.76 * 10 -4 1.02 * 10 -3
appendix - safety-related applications (sil 2) en version 04 phoenix contact a-4 ? the repair time (replacement) is eight hours. ? the failure rates of the external power supply unit are not taken into consideration. ? the average temperature at which the device is to be used is 40c. in this case, normal industrial conditions are assumed. ? the specified failure rates are based on an average am - bient temperature of 40c. for an average ambient temperature of 60c, the failure rates must be multiplied by factor 2.5. factor 2.5 is based on guide values. 1.2.4 failure rates: macx mcr(-ex)-t-ui-up(-sp) (-c) ? type b device (according to en 61508-2) ? safety integrity level (sil) 2 ?hft = 0 ? 1oo1d architecture the total failure rate is: 1.19 * 10 -6 the mtbf (mean time between failures) is therefore 96 years. the probability of a dangerous failure per hour for ?continu - ous demand? mode and the aver age probability of failure of the specified function for ?low demand? mode are deter - mined from the error rate: pfd avg values pfh* = 5.6 * 10 -8 /h the calculation is performed a ssuming a checking interval (t proof ) of 1 year and a repair time (mttr) of 24 hours, a test coverage (cpt) of 95% and a life time (lt) of 10 years. on the basis of the value dete rmined for the average proba - bility of failure pfd avg , the checking interval can be in - creased to up to 5 years. the values are valid under the following conditions: ? the failure rates of the components used remain con - stant throughout the period of use. ? the propagation of failures by the device in the system is not taken into consideration. ? the repair time (replacement) is eight hours. ? the failure rates of the external power supply unit are not taken into consideration. ? the average temperature at which the device is to be used is 40c. in this case, normal industrial conditions are assumed. ? the specified failure rates are based on an average am - bient temperature of 40c . for an average ambient temperature of 60c, the failure rates must be multiplied by factor 2.5. factor 2.5 is based on guide values. a1.3 configuring an sil device the measuring transducer can be ordered with a standard configuration (see 1.) or config ured for safety-related appli - cations (see 2.), or can be co nfigured by users themselves for safety-related ap plications (see 3.). 1. the measuring transducers are delivered with a stan - dard configuration for safety-r elated applications with a 4 - 20 ma output (see order key). 2. customer-specific pre-configured devices (-c) can be delivered for both safety-rel ated applications and ?nor - mal? usage. configuration data is shown on a label. 3. the measuring transducers ca n also be configured by users for both safety-related applications and ?normal? usage. the configuration can be read out and changed at any time for all devices. input: voltage input mv output: 4 ... 20 ma (current output) sd su dd du sff dc d 0 0 7.89* 10 -7 0.56 * 10 -7 93% 93% 0 fit 0 fit 789 fit 56 fit t[proof] = 1 year 2 years 5 years pfd avg = 3.75 * 10 -4 6.08 * 10 -4 1.31 * 10 -3 for safety-related applic ations, the password set in the factory must always be changed. if the password is lost, it is not possible to change the configuration. in this case, please contact phoenix contact.
appendix - safety-related applications (sil 2) en version 04 phoenix contact a-5 configuring safety-related applications ? connect the device and pc with the help of the ifs- usb-prog-adapter programming adapter (order no. 2811271). ? load the ifs-conf configur ation software (free down - load at: www.phoenixcontact.net/catalog ). further information on the fdt frame application (ifs- conf) and the device drivers (dtm) can be found in the ifs-conf user manual. ? read out the active configuration. ? enter the password in the ifs-conf in the ?pin? hard - ware configuration (set to 1111 in the factory). ? activate/deactivate sil. in the case of ? sil on? , it is also possible to deactivate the ? restart after failsafe? item here. this means that in the even t of a failure, the measuring transducer enters the failsafe state according to the safety functions, but is not restarted. ? write the modified configurat ion data to the measuring transducer. ? check that the new configur ation data in the control window is correct and confirm with ? ok? or ? cancel? if not correct. a1.4 installation and startup during installation, always observe the package slips the package slip is supplied with the device. it can also be downloaded at: www.phoenixcontact.net/catalog. lockable housing with ip54 protection is recommended for the installation of th e measuring transducer. ? check that the configuration of the measuring transduc - er is correct for the intended application. ? connect the measuring transd ucer according to the in - stallation instructions. ? make sure that the connected sensor corresponds to the configuration. ? check the functionality of the measuring transducer with connected sensor for correct function. a calibrated sensor simulator (rtd/tc) and a calibrat - ed digital multimeter are necessary for checking the measuring transducer. ? start up the loop and check that it operates correctly. a1.5 notes on operation only the green led (pwr) is on during normal operation. if a malfunction occurs duri ng operation and the red led (err) flashes, there is a line fa ult. the output current of the measuring transducer is between 2 ? 3.6 ma or is higher than 21.0 ma (in the case of faults in the sensor circuit) or is 0 ma (in the case of a line br eak in the output circuit). check all signal lines. the device will automatically switch back to normal operation after the fault has been eliminated. if a fault occurs during operation and the red led (err) is permanently on, the device has switched to the ?safe state? (output current is less than 2 ma). restart the device in order to return it to normal operation. ? if no pc/laptop has been connected, you can also inter - rupt the power supply. ? or you can carry out a warm start with the help of the configuration software ( service > reset ). the measuring transducer should then return to normal op - eration. if it does not, the measuring transducer must be re - placed. note: installation, operatio n, and maintenance may only be carried out by qualified specialist per- sonnel. warning: if functional safety is activated by a reconfiguration or changes are made to the active functional safety configuration, the rules under ?installation and startup? must be observed. warning: limitations on safety-related ap- plications only 4 ... 20 ma, limited programming of output current in the event of line faults (2 ma i out 3.6 ma or i out 21 ma) warning: once new configuration data has been written, the device performs a warm start that changes the properties of the device. the fol- lowing control device must be adapted to these modifications. warning: the device must be write-protected to prevent improper use. write protection is cre- ated by assigning a password. designation mnr no. packb.macx mcr-t-ui-up... 9055145 packb.macx mcr-ex-t-ui-up... 9055147 packb.macx mcr-t-uirel-up... 9055146 packb.macx mcr-ex-t-uirel-up... 9055148
appendix - safety-related applications (sil 2) en version 04 phoenix contact a-6 a1.6 recurring checks (sil 2) the function of the entire safety loop must be checked reg - ularly according to en 61508 and en 61511. the intervals for checking are specified by th e intervals of each individual device within the safety loop. it is the operator's responsibility to select the type of checks and the checking intervals in the specified time period. the measuring transducers must be checked at least every 7 years (maximum proof test interval). checking must be carried out in such a way that the correct function of the safety equipment in conjunction with all com - ponents can be verified. possible procedure for recurring checks for discover - ing dangerous and undetected device failures. a calibrated sensor simulator (rtd/tc) and a calibrated digital multimeter are necessary for checking the measuring transducer. ? connect the sensor simulator to the input of the mea - suring transducer using th e appropriate connection method. ? connect the digital multimeter to the output in current measuring mode (20 ma range). the measuring range limits an d intermediate values are specified with the sensor simulator. the corresponding output valu es of the measuring trans - ducer must be checked on the digital multimeter. line faults (break and short circuit) are to be simulated on the input terminals; the config ured residual currents are to be determined on the output. if the function test result is negative, the measuring trans - ducer must be taken out of operation and the process put into a safe state by other measures. a1.7 repair the devices have a long servic e life, are protected against malfunctions, and are maintena nce-free. however, if a de - vice should fail, send it ba ck to phoenix contact immedi - ately. the type of malfunction and possible cause must also be stated. please use the original packaging or other suitable safe packaging when sending devices back for repairs or recali - bration. phoenix contact gmbh & co kg abteilung service und reparatur flachsmarktstr. 8 d-32825 blomberg germany a1.8 standards (sil 2) the measuring transducers are developed and tested ac - cording to the following standards: en 61508: 2001 functional safety of electrical/electronic/ programmable electron ic safety-related systems en 61326-1: 2006 electrical equipment for measurement, control and laboratory use ? emc re - quirements iec 61326-3-2: 2006 electrical equipment for measurement, control and laboratory use ? emc re - quirements ? part 3-2: immunity require - ments for safety-related systems and for equipment intended to perform safety- related functions (functional safety) ? in - dustrial applications with specified elec - tromagnetic environment
appendix - safety-related applications (sil 2) en version 04 a-7 phoenix contact gmbh & co. kg ? 32823 blomberg ? germany www.phoenixcontact.com a1.9 abbreviations abbreviation meaning dc d diagnostic cov- erage of dan- gerous failures diagnostic coverage: dc d = dd /( du + dd ) hft hardware fault tolerance hardware fault tolerance: ability of a function unit to con- tinue with the execution of a de- manded function despite exist- ing failures or deviations d rate of danger- ous failures proportion of dangerous fail- ures per hour dd rate of danger- ous detected failures proportion of detected danger- ous failures per hour du rate of danger- ous undetected failures proportion of undetected dan- gerous failures per hour s rate of safe failures proportion of safe failures per hour mtbf mean time between failures mean time between consecu- tive failures pfd avg average probability of failure on demand average probability of failure on demand of a safety function pfh probability of a dangerous failure per hour probability of failure per hour for the safety function sff safe failure fraction proportion of safe failures: pro- portion of failures without the potential to set the safety-re- lated system to a dangerous or impermissible function state sil safety integrity level international standard iec 61508 defines four discrete safety integrity levels (sil 1 to 4). each level corresponds to a probability range for the failure of a safety function. the higher the safety integrity level of safety-related systems, the lower the probability that the demanded safety functions will not be performed.


▲Up To Search▲   

 
Price & Availability of 104601

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X